Commercial fire doors installed & maintained.
Fire door and steel fire exit door installation for offices, retail, industrial and managed premises. Every visit is photographed and logged in software, giving you a complete, traceable record of the work.
Protecting people, premises and escape routes.
In a commercial building, every fire door forms part of a wider fire strategy. The leaf, frame, seals, hinges, closer, latch and gaps must work as one tested system to help contain fire and smoke while protecting escape routes.
We fit and repair fire doors to Approved Document B and BM TRADA guidance. That means correct intumescent seals, smoke seals, certified hinges, self-closers that actually close the door, and gap tolerances that an inspector will pass.
From a single replacement to a planned programme across multiple premises, we coordinate work around occupants and operations, then provide a clear digital record for your compliance files.

Commercial installation, repair & compliance checks.
Commercial installation
New FD30 and FD60 door sets installed for offices, retail premises, industrial units and managed buildings, with the correct frame, seals, closer and certified ironmongery.
Remedial repairs
We repair or replace seals, closers, hinges, locks and handles to bring existing doors back to the required standard without full replacement where appropriate.
Digital traceability
Every visit is logged with dated photos, itemised checks and sign-off records, giving facilities teams, duty holders and managing agents a clear audit trail.
Gap & seal checks
We measure and adjust the critical gaps around the leaf, threshold and frame, the detail that most often causes a fire door to fail an inspection.

Steel fire exit doors built for demanding sites.
We supply and install robust steel fire exit and fire-rated door sets for warehouses, factories, plant rooms, service areas and other commercial premises. Each opening is surveyed so the door, frame and hardware suit its fire, security and access requirements.
Exit hardware
Panic bars, emergency exit devices, closers and external access options specified for the doorway.
Commercial durability
Single and double steel door sets suited to busy, exposed and security-sensitive locations.
Reported in software. Proof of compliance.
Photographic record
Before, during and after photos of each door, frame, seal and closer are uploaded against the job record.
Itemised checklist
Each component is checked against a compliance checklist so nothing is missed or assumed.
Shareable reports
Reports can be shared with duty holders, facilities teams, managing agents or building control whenever required.
What we inspect on every door.
Door leaf condition
No damage, holes or unauthorised glazing that would compromise the rating.
Frame & lining
Frame is secure, correctly fitted and packed with fire-resistant material.
Intumescent & smoke seals
Seals are present, continuous and undamaged around the frame and door edges.
Hinges & hardware
Minimum three CE-marked fire hinges; locks and handles do not weaken the door.
Self-closing device
Door closes fully and latches from every open position without sticking.
Threshold gaps
Gap at the bottom is within 3–4 mm where a threshold seal is fitted, or 8–10 mm max without.
From survey to sign-off.
Site survey
We inspect each door, frame and hardware item, measure gaps and photograph the current condition.
Quote & spec
A fixed-price quote listing replacement or remedial items, ratings and completion timeframe.
Installation / repair
Doors fitted or remedial items replaced to BM TRADA standards, with photos logged at each stage.
Digital report
A signed-off, cloud-stored report with photos and checklist results delivered to you.
Fire door questions.
- What types of commercial premises do you work in?
- We install and repair fire doors in offices, shops, warehouses, industrial units, schools, care settings, communal buildings and managed properties across Nottingham. Each project is planned around the building, its fire strategy and day-to-day access requirements.
- What is fire door remedial work?
- Remedial work brings an existing fire door back to compliance. Common issues we fix are damaged or missing intumescent strips, over/under-sized gaps around the door leaf, failed closers, missing or non-compliant hinges, and doors that no longer self-close or latch properly.
- How do you report and document the work?
- We record every installation and remedial visit using job management software. This gives you a time-stamped, photographic report covering before, during and after works, plus a checklist of every fire-door element inspected or replaced. Reports are stored securely and can be shared with landlords, managing agents or building control.
- How long does a fire door installation take?
- A straightforward replacement in an existing frame usually takes half a day per door. New openings, or doors that need the frame replaced or upgraded, typically take one to two days. We always confirm timings during the site survey.
- Do you install steel fire exit doors?
- Yes. We supply and install steel fire exit and fire-rated steel door sets for commercial and industrial premises. The specification can include single or double leaves, panic bars, external access hardware, closers and security options, selected to suit the opening and the building's fire strategy.
Need a fire door survey in Nottingham?
Tell us about the building, the number of openings and any recent inspection findings. We will arrange a survey and provide a clear proposal for installation or remedial works.